Regulations

IEC62034 Automated testing systems for emergency lighting

BS EN50172/BS5266

BS EN60598

FSD Code of Practice for Inspection, testing and maintenance of installation and equipment

FSD PPA104(A) 4th rev

According to FSD and BS EN requirements, all self-contained battery emergency lighting including exit signs shall be operated by battery, in power outage, by at least one hour.  Battery test shall be done as per following schedule:

Monthly:         <¼ of rated duration (1 min)

6-monthly:      ¼ of rated duration (15 min)

Annually:        Full duration (1 hour) [BS EN50172/BS5266]

36-monthly:    Full duration (1 hour)